< BACK TO CASE STUDIES

PowerFog® Case Study

logo-duke

DUKE ENERGY

New Albany Peaking Plant
6x7E Combustion Turbines
New Albany, MS

PowerFog® Design Ratings

Ambient Conditions
100°F Dry Bulb Temp
78°F Wet Bulb Temp

Cool to Temperature
79°F

Airflow at 79°F
2,217,528 lbs/hr/turbine

Net Capacity Increase
33 MW

Major System Components

(18) SS HP Triplex Pumps
(3) AB 504 Programmable Logic Controllers
(3) Solid State Dew Point Transmitters
(1,320) PowerFog® HP nozzles
Integrated Generator Cooling System
(3) 20,000 Gallon FRP Demin Water Storage Tanks

Pressure Drop

< 0.25 in. w.c. across nozzle manifolds

Cooling Capacity

21°F

Design Cooling Control

1°F

System Installation

Caldwell Energy & Environmental, Inc. Turnkey