EL PASO CORPORATION
Camden Cogen
1x7EA Combined Cycle
PowerChill® Design Ratings
Ambient Conditions
72°F Dry Bulb Temp
66°F Wet Bulb Temp
Cool to Temperature
50°F
Airflow at 79°F
2,353,551 lbs/hr
Net Capacity Increase
10 MW
Major System Components
Chiller: 2,000 Tons Centrifugal
Refrigerant: R-134a
Cooling Coils: 10 (2,035 Tons) Finned Tube
Glycol Pumps: 2 x 350 HP (one stand-by)
Cooling Water Pumps: 2 x 250 HP (one stand-by)
Condensate Pumps: 2 x 3.5 HP (one stand-by)
Glycol Storage Tank: 4,000 Gallons
System Guarantees
Airside pressure drop
< 1.0 in. w.c.
Auxiliary Power Consumption
< 1,942 kW
Turbine Inlet Temperature
50°F
System Installation
Caldwell Energy & Environmental, Inc. Turnkey